05/28/2019 | 022-FOOTINGS/PIERS | RAMON VALENCIA | NOT READY | 181887_190523092926.wav | |
|
10/08/2019 | 022-FOOTINGS/PIERS | MICHAEL EMERY | NOT READY | eTRAKiT Inspection Request | 10/7/2019 4:07:52 PM
10/7/2019 4:07 PM John Palmer
Contact Name: John Palmer
Site Address: TRACY HILLS PUBLIC PARK # 1
Phone: 2096391642
e-Mail: johnpalmer@integralcommunities.com
10/8/2019 3:46:02 PM
NOT READY
|
|
10/09/2019 | 022-FOOTINGS | MICHAEL EMERY | APPROVED | | |
|
11/26/2019 | 130-ALL FINALS** | MICHAEL EMERY | NO ACCESS | | 11/26/2019 2:33:03 PM
Gated around entire area with nobody on site.
|
|
12/03/2019 | 130-ALL FINALS** | RAMON VALENCIA | NO ACCESS | Please call before! 916-533-3591 | 12/3/2019 9:45:34 AM
Contractor not on site.
|
|
12/04/2019 | 140-FINAL ACCESSIBIL | STEVE MONCUR | CORRECTION NOTICE | | 12/4/2019 11:33:34 AM
Information only given to Tom
No handle ties on breakers
Both pedestal not labeled
Load exceeds amps and over current protection
Missing caps for conduit at both pedestal
Remove main bonding jumper at stainless pedestal
Underground conduit not accounted for needs pot holing
Bath load center needs to be handle tried
Single one does show main sizes for feeder and over current load is 58.38 installed is a 20 amp
Top off plumbing
No records of footing or underground electrical
Remove electrical covers for inspection
No plans on site for shade structure
Advised we need electrician on site for inspection
|
|
12/04/2019 | 130-ALL FINALS** | RAMON VALENCIA | CANCELLED | | |
|
12/05/2019 | 132-FINAL BLDG** | MICHAEL EMERY | APPROVED | | 12/5/2019 3:42:47 PM
SHADE STRUCTURE AND TABLES ONLY.
|
|
12/05/2019 | 140-FINAL ACCESSIBIL | STEVE MONCUR | APPROVED | | |
|