12/03/2019 | 134-FINAL ELEC** | SHAIN NIVEN | CORRECTION NOTICE | | 12/3/2019 1:28:17 PM
Update plans to show line side tap at Main panel
Plans call for a 30 amp disconnect at inverter location, as built 60 amp installed.
Rapid shut down test still needed.
At roof top, repair short section of conduit, conduit run does not fully reach the rain tight fittings.
Grounding wire is not installed at all Arrays, repair as needed.
Note: CO form collected.
|
|
01/27/2020 | 134-FINAL ELEC** | SHAIN NIVEN | APPROVED | | |
|
|
|
|