04/14/2021 | FINAL SOLAR** | WLADYSLAW GROBELNY | CORRECTION NOTICE | | 4/14/2021 7:46:47 PM
1. Ground wire damaged at the bonding bushing, solar disconnect panel
2. Two double 15 amp breakers with conductors run from the main service panel in the solar conduit. 14 awg conductors shall run in a separate conduit.
3. Knock out not covered
4. Roof not inspected
5. Rapid shut down test not performed- no tools
|
|
05/04/2021 | FINAL SOLAR** | JAMES ALLISON | CORRECTION NOTICE | eTRAKiT Inspection Request | 4/28/2021 10:43:42 AM
4/28/2021 10:43 AM MYERS ELECTRIC COMPANY INC
Contact Name: Brett
Site Address: 98 PRIMROSE CT
Phone: 5302109910
e-Mail: lizklapp.myerselectric@gmail.com
5/4/2021 1:09:24 PM
Four 15 amp breakers relocated into emphase combiner. Provide specs showing listing for combiner panel, showing relocated loads allowed in combiner panel.
If circuits can be relocated to combiner, then conductors shall be separated since breakers cannot be derated. Also, neutrals for these circuits shall terminate at combiner neutral bus and each circuit shall be identified. Provide handle ties if neutrals are shared.
Or, provide sub panel for solar breaker and relocated loads.
Revise plans showing final install.
All other ok.
|
|
05/04/2021 | FINAL BUILDING** | JAMES ALLISON | CORRECTION NOTICE | PM Requested | 4/20/2021 4:06:29 PM
4/20/2021 4:06 PM MYERS ELECTRIC COMPANY INC
PM request
Contact Name: Brett
Site Address: 98 PRIMROSE CT
Phone: 5302109910
e-Mail: lizklapp.myerselectric@gmail.com
4/28/2021 11:03:29 AM
4/28/2021 11:03 AM MYERS ELECTRIC COMPANY INC
PM requested
Contact Name: Brett
Site Address: 98 PRIMROSE CT
Phone: 5302109910
e-Mail: lizklapp.myerselectric@gmail.com
|
|
07/01/2021 | FINAL SOLAR** | JIM DECKER | APPROVED | eTRAKiT Inspection Request | 6/25/2021 11:52:48 AM
6/25/2021 11:52 AM MYERS ELECTRIC COMPANY INC
Contact Name: MYERS ELECTRIC COMPANY INC
Site Address: 98 PRIMROSE CT
Phone: 9512132108
e-Mail: MyersPermitting@gmail.com
|
|