On the day of a scheduled inspection, customers can call the City of Tracy at 209-831-6400 any time after 8:00 a.m.  The City of Tracy will then give you the assigned inspector’s name and cell phone number.  Customers can then contact the inspector to get an estimated timeframe as to when the inspector will arrive for the inspection.

 
Permit No. RES21-0461 Permit Type   PHOTOVOLTAIC Site Address   98 PRIMROSE CT
TRACY, CA 95376
Applied   03/01/2021 Applicant   MYERS ELECTRIC COMPANY INC
Approved   03/19/2021 Owner   ARAUJO DOUG ALLEN & ARAUJO LAUREN MICHELE
Issued   03/23/2021 Contractor   MYERS ELECTRIC COMPANY INC
Parent Permit No.   Description   8.280KW ROOF-MOUNT PV, DERATE MAIN-100A & (N) SUBPANEL
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 04/14/2021FINAL SOLAR**WLADYSLAW GROBELNYCORRECTION NOTICE4/14/2021 7:46:47 PM 1. Ground wire damaged at the bonding bushing, solar disconnect panel 2. Two double 15 amp breakers with conductors run from the main service panel in the solar conduit. 14 awg conductors shall run in a separate conduit. 3. Knock out not covered 4. Roof not inspected 5. Rapid shut down test not performed- no tools

 05/04/2021FINAL SOLAR**JAMES ALLISONCORRECTION NOTICEeTRAKiT Inspection Request4/28/2021 10:43:42 AM 4/28/2021 10:43 AM MYERS ELECTRIC COMPANY INC Contact Name: Brett Site Address: 98 PRIMROSE CT Phone: 5302109910 e-Mail: lizklapp.myerselectric@gmail.com 5/4/2021 1:09:24 PM Four 15 amp breakers relocated into emphase combiner. Provide specs showing listing for combiner panel, showing relocated loads allowed in combiner panel. If circuits can be relocated to combiner, then conductors shall be separated since breakers cannot be derated. Also, neutrals for these circuits shall terminate at combiner neutral bus and each circuit shall be identified. Provide handle ties if neutrals are shared. Or, provide sub panel for solar breaker and relocated loads. Revise plans showing final install. All other ok.

 05/04/2021FINAL BUILDING**JAMES ALLISONCORRECTION NOTICEPM Requested4/20/2021 4:06:29 PM 4/20/2021 4:06 PM MYERS ELECTRIC COMPANY INC PM request Contact Name: Brett Site Address: 98 PRIMROSE CT Phone: 5302109910 e-Mail: lizklapp.myerselectric@gmail.com 4/28/2021 11:03:29 AM 4/28/2021 11:03 AM MYERS ELECTRIC COMPANY INC PM requested Contact Name: Brett Site Address: 98 PRIMROSE CT Phone: 5302109910 e-Mail: lizklapp.myerselectric@gmail.com

 07/01/2021FINAL SOLAR**JIM DECKERAPPROVEDeTRAKiT Inspection Request6/25/2021 11:52:48 AM 6/25/2021 11:52 AM MYERS ELECTRIC COMPANY INC Contact Name: MYERS ELECTRIC COMPANY INC Site Address: 98 PRIMROSE CT Phone: 9512132108 e-Mail: MyersPermitting@gmail.com